We replaced our raised floor tiles some time ago. There's a phenomenonMany years ago, I lost the power supplies in a couple routers while
called 'zinc threads'. These form on galvanized metal, such as that found
on the bottom of computer room tiles. Lost six power supplies during the
change out. IBM central dispatch asked me if I was just changing my floor
tiles. I asked them how could they figure that out. They said tile
changes are the only time they've seen people lose multiple power supplies
like this.
As an Amazon Associate we earn from qualifying purchases.
This mailing list archive is Copyright 1997-2024 by midrange.com and David Gibbs as a compilation work. Use of the archive is restricted to research of a business or technical nature. Any other uses are prohibited. Full details are available on our policy page. If you have questions about this, please contact [javascript protected email address].