I would NOT use the router as your ground point, that would force any
electrical fault THROUGH the router, in effect electrocuting it.
I think you're going to need a ground wire to replace that short strap that
will go down to the bottom. The rack ground lug is in the back at the
bottom.
--
Jim Oberholtzer
Agile Technology Architects
-----Original Message-----
From: MIDRANGE-L [mailto:midrange-l-bounces@xxxxxxxxxxxx] On Behalf Of Rob
Berendt
Sent: Wednesday, April 12, 2017 9:47 AM
To: midrange-l@xxxxxxxxxxxx
Subject: How to ground an IBM 36U rack?
We are installing equipment into a data center. Suspended above the rack is
a ground cable with a terminal at the end with two inline holes.
There's not a whole lot of slack in that cable. Barely reaches the 36U
rack. I think we're the only company there using IBM racks and I think most
others are using 42U racks.
Is there a suggested place to attach a ground cable on a 36 U rack? Or, is
it common practice to not ground the rack but instead use it as a lug on to
a router? I notice some of our Cisco routers come with a ground lug
attached to the side for you to crimp a cable into. The holes in the
terminal on the suspended cable look like a possible match.
Rob Berendt
--
IBM Certified System Administrator - IBM i 6.1 Group Dekko Dept 1600 Mail
to: 2505 Dekko Drive
Garrett, IN 46738
Ship to: Dock 108
6928N 400E
Kendallville, IN 46755
http://www.dekko.com
--
This is the Midrange Systems Technical Discussion (MIDRANGE-L) mailing list
To post a message email: MIDRANGE-L@xxxxxxxxxxxx To subscribe, unsubscribe,
or change list options,
visit:
http://lists.midrange.com/mailman/listinfo/midrange-l
or email: MIDRANGE-L-request@xxxxxxxxxxxx Before posting, please take a
moment to review the archives at
http://archive.midrange.com/midrange-l.
Please contact support@xxxxxxxxxxxx for any subscription related questions.
Help support midrange.com by shopping at amazon.com with our affiliate link:
http://amzn.to/2dEadiD
As an Amazon Associate we earn from qualifying purchases.