The short term solution is to pull the cable from the UPS to the 270. Of course this way if there is a real power outage you run until those weak old batteries area actually dead and then 'thud'.

Better would be a program handing the power rather than IBMs build in code. This way you can do whatever you want. Set a message queue other than QSYSOPR (something like QUPSMSGQ for example) .and then set a break handling program on queue. The program then does what YOU want it to do.

Best of course is new batteries. But you knew that. :-)

- Larry



Pete Helgren wrote:
It is set for 300 on this 270. I *think* that means that it should wait for 5 minutes before beginning the shutdown but it appears that when it detects a "weak battery condition" then it ignores the value and just shuts down on its own.

Pete


Lukas Beeler wrote:
What's your System Value QUPSDLYTIM set to?

It should _NEVER_ be on *CALC with "normal" Systems. I usually have set
it to 300.

*CALC is only used for Systems with an internal UPS. Those no longer
exist. And the 270 didn't have an internal UPS.




As an Amazon Associate we earn from qualifying purchases.

This thread ...

Follow-Ups:
Replies:

Follow On AppleNews
Return to Archive home page | Return to MIDRANGE.COM home page

This mailing list archive is Copyright 1997-2024 by midrange.com and David Gibbs as a compilation work. Use of the archive is restricted to research of a business or technical nature. Any other uses are prohibited. Full details are available on our policy page. If you have questions about this, please contact [javascript protected email address].

Operating expenses for this site are earned using the Amazon Associate program and Google Adsense.